HG-3C single-phase electric energy meter field verification device


With the large-scale promotion of the use of single-phase smart meters by the State Grid, problems with the use of on-site smart meters have also increased. Conventional single-phase calibrators can no longer meet the use requirements of front-line maintenance personnel. In response to this phenomenon, our company has developed The HG-3C single-phase electric energy meter field calibration device is introduced. It has the functions of a single-phase electric energy meter field calibrator and a single-phase electric energy meter inspection device. It is a good assistant for front-line maintenance personnel.

  • Product description
  • I. Overview

    With the large-scale promotion of the use of single-phase smart meters by the State Grid, problems with the use of on-site smart meters have also increased. Conventional single-phase calibrators can no longer meet the use requirements of front-line maintenance personnel. In response to this phenomenon, our company has developed The HG-3C single-phase electric energy meter field calibration device is introduced. It has the functions of a single-phase electric energy meter field calibrator and a single-phase electric energy meter inspection device. It is a good assistant for front-line maintenance personnel.

    2. Main features and functions

    1. The device adopts an integrated structure of meter and source, and can be connected to a three-meter hanging meter stand (the first meter adopts a meter stand that conforms to the State Grid smart meter wiring method, and the other meter locations are conventional aluminum alloy meter stands, using crimped wiring. method); it can also be used as a field calibrator on site.

    2. The host adopts a 7-inch color TFT touch screen (resistive screen, which can be clicked with fingertips), ARM embedded system, WINCE operating system, the signal source adopts STM RAM system, and a large-scale FPGA outputs 36,000 points of 12-bit DDS synthetic waveform, 16-bit D/A amplitude modulation output has the advantages of high stability and low distortion.

    3. The entire device consists of a program-controlled digital synthesized harmonic signal source, a Class D power amplifier, a meter rack with built-in isolation PT for three meters, a single-phase multi-function standard meter, a time reference source, a multi-function meter processor, and an intelligent electric energy meter. It is composed of test module, communication test module, current clamp and calibration management software platform.

    4. The programmable source, power amplifier, voltage and current generator and other modules are all modular in design, which facilitates the quick disassembly, assembly and maintenance of each functional unit. Using high-efficiency pulse width modulation technology, the output voltage (current) has high efficiency, low heat generation, good stability, and low failure rate.

    5. The device has complete protection functions, including current open circuit, overload protection, voltage short circuit protection and other functions.

    6. Equipped with a dedicated clock reference of the GPS module and a built-in 2×10-7 high-precision constant-temperature crystal oscillator, it is used to test the clock pulse output accuracy of smart meters. It can also calculate daily timing errors and accurately time smart meters.

    7. It can test the measurement functions of smart meters, including creeping, starting, basic error, standard deviation, constant calibration, error variation, error curve, combined error, etc.

    8. The demand indication error test can be carried out using the standard electric energy method and the standard power method.

    9. With the management software, the freezing function of the smart meter can be tested, and various freezing methods can be tested.

    10. The timing and rate functions of the smart meter can be tested in the management software, including time adjustment, daily timing error, calendar, rate setting and switching, step electricity price setting and switching, etc.

    11. The demand period error test can be carried out through the cumulative power method or the demand output pulse.

    12. The period switching error test can be carried out through the cumulative power method or switching output pulse.

    13. The event recording function of the smart meter can be tested, including loss of voltage, loss of current, phase loss, total loss of voltage, power outage, programming, clearing, switch cover, power off, etc.

    14. Tests such as voltage drop, power interruption, and power supply ramp-up and ramp-down can be carried out.

    15. It can test the RS485 interface of the smart meter and check the communication protocol consistency of the smart meter.

    16. It has the cost control function test and supports two types of energy meters: local cost control and remote cost control (requires network testing).

    17. The trip relay can be tested.

    18. The 2nd to 21st harmonics can be superimposed, and the amplitude and phase can be set freely. Harmonic analysis can also be performed on the output and waveforms can be drawn.

    19. The device self-test function can be optionally configured to monitor the voltage, current, phase, power factor, frequency, output harmonic waveform, power stability and other indicators of the device.

    20. Optional infrared communication head can be used for infrared communication testing.

    21. PC control management software, with simple and clear interface, full menu graphic mode, easy to learn and use. Database query, statistics, printing and networking are all available. anchor point

    3. Main technical indicators and technical performance

    3.1 Device accuracy level: 0.1 level;

    With 100A clamp meter Accuracy level: 0.2

    3.2 Built-in single-phase multi-function standard electric energy meter indicators:

    ● Accuracy level: 0.1 level

    ●Input current range: 100A, 50A, 20A, 10A,

    5A, 2.5A, 1A, 0.5A, 0.25A, 0.1A, 0.05A, 0.025A

    Input voltage range: 300V
    Display digits: 6 significant digits

    3.3 Output voltage: 220V (the user can choose between 100V ~ 240V)

    The adjustment range is continuously adjustable from 0 to 120%

    Adjustment fineness: better than 0.01%

    3.2 Output current range: 0.1A, 1A, 5A, 20A, 100A.

    The adjustment range is continuously adjustable from 0 to 120%

    Adjustment fineness better than 0.01%

    Minimum output current: 1mA (≤5%)

    3.3 Output power: 3 meters, (voltage loop) 50VA

     (Current loop) 100VA

      3.4 Output voltage, current and power stability;

    ≤0.05%/120S

    3.5 Output voltage and current waveform distortion: ≤ 1%

    3.6 Frequency range: 45Hz~65Hz

    Adjustment fineness: 0.01Hz

    3.7 Phase shift range: -180.0o ~ 180.0o

    Adjustment fineness: 0.01o

    3.8 Indicating instrument level: standard meter display accuracy.

    3.9 Current clamp: 100A, accuracy: 0.2 level

    3.10 Power supply: AC 220V±10%~50Hz

    3.11 Maximum power consumption: 200VA

    3.12 Working environment: temperature -10℃ ~ 40℃ ± 5℃;

    Relative humidity ≤85%

    Keywords:
    • 测试
    • 电流
    • 输出
    • 进行
    • 智能
    • 功能
    • 可以
    • 电压
    • 装置